Vertical

NYC vertical series are highly efficient air conditioning units with heat pump or cold-only operation for medium and high capacity applications, such as supermarkets, leisure areas, shops, production plants, offices or malls.

These vertical units are designed to be installed inside buildings, normally in engine rooms, and to be joined to a network of ducts inside (area to be air-conditioned) and outside (heat dissipation).

NYC series go from 13 to 92 kW, and are available in a compact and split version. Full configurable and with a wide range of options, these are the ideal invisible solution for buildings where units cannot be installed outdoors.

The INVERTER compressor allows to precisely adjust the capacity of the equipment to a specific thermic demand of the installation, consuming only the necessary electrical capacity at all times.

All our equipments comply with the most demanding regulations (ERP2021).

VERTICALS NEW YORK INVERTER

MODEL  NYC020NYC025INVERTER
i-NYC025
NYC035INVERTER
i-NYC035
NYC045INVERTER
i-NYC045
NYC050NYC065
COOLING MODE SYSTEM
Total cooling powerPCkW21.825.522.936.536.343.143.049.065.4
Useful power absorbed in coolingPEkW7.08.48.910.712.013.913.013.719.3
Coefficient of energy efficiency in coolingEERW/W3.103.032.583.413.033.103.303.573.40
SEERSEERW/W--3.49-3.67-4.66--
Seasonal energy efficiency
Ƞs,c%--140-147-186--
HEATING MODE SYSTEM
Total heating powerPHkW21.424.923.536.037.242.844.148.064.1
Useful power absorbed in heatingPEkW6.67.88.010.010.712.711.512.618.0
Coefficient of energy efficiency in heatingCOPW/W3.263.192.943.603.473.353.833.803.57
SCOPSCOPW/W--4.17-4.43-4.85--
Seasonal energy efficiency
Ƞs,h%--164-174-191--
COMPRESSORS
Type of compressorScrollScrollScroll Inverter DCScrollScroll Inverter DCScrollScroll Inverter DCScrollScroll
EXTERIOR UNIT FAN
Fan TypeCentrifugal ECCentrifugal ECRadial ECCentrifugal ECRadial ECCentrifugal ECRadial ECCentrifugal ECCentrifugal EC
Airflowqem³/h710076008000105001160013000140001480018400
Available static pressure of the equipmentpedPa412276196167475531368377313
INTERNAL UNIT FAN
Fan TypeCentrifugal ECCentrifugal ECCentrifugal ECCentrifugal ECCentrifugal ECCentrifugal ECCentrifugal ECCentrifugal ECCentrifugal EC
Airflowqim³/h4000480050007000750079007000970012000
Available static pressure in the equipmentpedPa616437874412290178470257636
GENERAL CHARACTERISTICS
Power supply400V-III+N-50Hz400V-III+N-50Hz400V-III+N-50Hz400V-III+N-50Hz400V-III+N-50Hz400V-III+N-50Hz400V-III+N-50Hz400V-III+N-50Hz400V-III+N-50Hz
RefrigerantR410AR410AR410AR410AR410AR410AR410AR410AR410A
Sound pressure level dB(A)--95.2-97.1-92.6--
Cooling power at nominal conditions of internal temperature of DBT= 27ºC, WBT = 19ºC and an external temperature of DBT = 35ºC, according to UNE-EN 14511 standard.

Heating power at nominal internal temperature conditions of DBT = 20ºC, WBT = 15ºC max., and an external temperature of DBT = 7ºC, WBT = 6ºC, according to UNE-EN 14511 standard.